Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ARD2M motor protector (hereinafter referred to as the protector) is suitable for low-voltage motor circuits with rated voltage up to 380V and integrates protection, measurement, control, communication, operation and maintenance.Its perfect protection function ensures the safe operation of the motor, with logic programmable function, can meet a variety of control methods.
Features
Protector
current specification (A) |
Ratio
setting |
Primary side coil
number of transformer |
Applicable scope of
motor (kW) |
Suitable for motor
Rated current range (A) |
1
|
Support
|
1 circle
|
0.12-999
|
0.1-1.6
|
5
|
1 circle
|
0.12-999
|
1.6-6.3
|
|
25
|
Does not
support |
1 circle
|
3-11
|
6.3-25
|
100
|
1 circle
|
15-45
|
25-100
|
|
250
|
1 circle
|
55-132
|
63-250
|
|
800
|
1 circle
|
160-250
|
250-800
|
Technical parameters
|
Technical indicators
|
|||
Protector auxiliary power supply
|
AC85-265V/DC100-350V
|
|||
Rated working voltage of the motor
|
AC220V / 380V,50Hz / 60Hz
|
|||
Rated operation current of the motor |
1 (0.1A-1.6A)
|
Integrated/Split current transformer |
||
5 (1.6A-6.3A)
|
||||
25(6.3A-25A)
|
||||
100(25A-100A)
|
||||
250(63A-250A)
|
Split current transformer
|
|||
800(250A-800A)
|
||||
Relay output contact capacity
|
Impedance load
|
AC250V,10A
|
||
Switching input
|
8 channels of passive dry contact (active DC110V, DC220V, AC220V
input can be optional) |
|||
Communication
|
RS485 Modbus_RTU,Profibus DP
|
|||
Environment |
Working temperature
|
-10ºC~55ºC
|
||
Storage temperature
|
-25ºC~70ºC
|
|||
Relative temperature
|
≤95 No condensation, no corrosive
gas |
|||
Altitude
|
≤2000m
|
|||
Pollution levels
|
3 level
|
|||
Protection grade
|
IP65(installed on the cabinet panel)
|
|||
Installation category
|
III Level
|