AMC seres meters adopt AC sampling technology, which can measure the curent yvoltace,power, power factor and electric energy parameters in the power grioseparately. t can set the magnification through the panel membrane switch. The meters have RS485 communication interface, adopt Modbus protocol also canconvert the power signal into a standard DC analog signal.
Technical parameters
|
Value
|
|||
Input
|
Connection
|
Single phase-2-wire,3-phase-3-wire,3-phase-4-wire
|
||
Frequency
|
45-65Hz
|
|||
Voltage
|
Rating:single-phase:AC100V,400VT
hree-phase:AC3×57.7V/100V(100V),3×220V/380V(400V),3×380V/660V(660V)(96sizeonly) Note:72 profile not suitable for high voltage applications |
|||
Overload:1.2foldrating{continuous):2foldratingfor1second
|
||||
Power consumption:<0.5VA
|
||||
Current
|
Rating:ACIA,5A
|
|||
Overload:1.2 fold rating(continuous);10fold rating for 1second
|
||||
Power consumption:<0.5VA
|
||||
Output
|
Electric energy
|
Output mode:open-collect or photo-coupler pulse
|
||
Pulse constant:10000 imp/kWh(settable),see wiring diagram for details;
|
||||
Communication
|
RS485 port,Modbus-RTU protocol, DLT645 protocol (versions 07 and 97),baud rate1200~38400
|
|||
Function
|
Switching input
|
Dry contact input,built-in power supply;
|
||
Switching output
|
Output mode:Relay normally open contact output
|
|||
Contact capacity:AC250V/3A,DC30V/3A
|
||||
Analog output
|
1-5V,4-20mA
|
|||
Accuracy class
|
Frequency:0.05Hz,Current,Voltage:0.2class,Reactive power:l.0class,Reactive Electric energy:l.0class, active power:0.5class, active
electric energy:0.5class,2-31th harmonic measurement:±1% |
|||
Power supply
|
AC/DC85-265V
|
power consumption≤10VA
|
||
Security
|
Powerfrequencywithstandvoltage
|
Between Power supply// Switching Output// Current Input// voltage Input and Transmitting// Communication// Pulse Output//
switching input AC2kV 1min;Between Power supply,switching output,Current Input,voltage Input AC2kV1min;Between Transmitting,Communication,Pulse Output,switching inputAC1kV1min; |
||
Insulationresistance
|
Input,Output end to machine enclosure>100MΩ
|
|||
Environment
|
Temperature
|
work:-25°C~+65°C storage:-40°C~+80°C
|
||
Humidity
|
≤93%RH Non-condensing
|
|||
Altitude
|
≤2500m
|