Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Usage: | Multi-Functional Energy Meter |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AMC16Z series AC precision power distribution monitoring device is specially designed for data center server power management.The device designed exquisite, can provide A + B 2 incoming and 96 outgoing's electrical parameters, the input and output switch and the state of lightning protection device with real-time monitoring. All alarm threshold of measurement channels can be set in separate. Over-outgoing triggers system acoustooptic warning immediately. Highly integrated monitoring loop is realized in the volume of traditional instruments.
Type Model
|
Function description
|
AMC16Z-ZA |
Monitor the full power parameters of A+B double-way three-phase AC incoming circuit, 6-way switch state monitoring, 2-way alarm
output, 2-way leakage monitoring, 1-way temperature and humidity detection, 1-way RS485 communication, and phase-sequence detection. |
AMC16Z-FA |
Monitor the full power parameters of 24 branches of A+B double-way AC outgoing line, 1-way RS485 communication and phase
adjustment. |
AMC16Z-KA
|
Wet contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication.
|
AMC16Z-KD
|
Dry contact, monitoring A+B total 48 branch switch state, 1-way RS485 communication.
|
AMC16Z-FAK24 |
Monitor the full power parameters and switch state of 24 branches of A+B double- way AC outgoing line, 1-way RS485 communication
and phase adjustment. |
AMC16Z-FAK48 |
Monitor the full power parameters and switch state of 48 branches of A+B double- way AC outgoing line, 1-way RS485 communication
and phase adjustment. |
AMC16Z-FDK24 |
Monitor the full power parameters and switch state of 24 branches of A+B double-way DC outgoing line, 1-way RS485 communication
and phase adjustment. |
AMC16Z-FDK48 |
Monitor the full power parameters and switch state of 48 branches of A+B double-way DC outgoing line, 1-way RS485 communication
and phase adjustment. |
Function
|
Description
|
Measurement
(Common) |
Three-phase AC kWh, kVarh, Active Power, Reactive Power, Current, Voltage, Power Factor, Apparent Power, Frequency, Zero ground
voltage, neutral line current |
Measurement
(Power Quality) |
total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest
coefficient (CF), telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity |
Temp.&Humidity
Monitoring |
Temperature Monitoring Range: -40ºC~+99ºC
Humidity Monitoring Range: 20%~90% |
Leakage Current
|
2-channel Leakage Current Measurement
|
Accuracy
|
Electrical Parameter Metering Accuracy: Voltage/current level 0.2, active power/electric energy level 0.5, reactive power/electric
energy level 1 Temperature Metering Accuracy: ±1ºC; Temperature Metering Accuracy: ±5% |
Communication
|
RS485 Interface (MODBUS-RTU protocol)
|
DO
(Switch Output) |
2-channel DO (Digital Output); 3A 250VAC/3A 30VDC
|
DI
(Switch Input) |
6-channel DI (Digital Input); dry contact
|
Parameter
|
Description&Value
|
|
Voltage
Input |
Rated Voltage
|
3x220~264Vac L-N
|
Reference Frequency
|
45~65Hz
|
|
Current
Input |
Rated Current
|
3x1(6)A AC (via CTs)
|
Power
Supply |
Source from
|
Voltage Input (Voltage signal input for both measurement and power supply)
|
Installation
|
DIN-rail
|
35mm standard DIN-rail Installation
|
Phase
Wiring |
3P4W
|
3-phase 4-wire
|
Safety
|
Insulation
|
All terminals and the insulation resistance between the conductive pieces not less than 100MΩ
|
Withstand voltage
|
A-way voltage and current signal, B-way voltage and current signal, switch output and other ports should meet AC2kV 1min in pairs,
the switch input and other ports should meet ac0.5kv 1mim, leakage current should be less than 2mA, no breakdown or flashover |
Condition
|
Description&Value
|
Temperature
|
Operating Temperature: -20ºC~+55ºC; Storage Temperature: -40°C ~+70°C
|
Humidity
|
≤95%RH, no condensation, without corrosive gas
|
Altitude
|
≤ 2000m
|