AM5 series microcomputer protection device are applicable to the user substation which the input voltage is 35kv or above. AM5 can be used to protect and control the user substation, and is be widely used to Power Industry, Water conservancy industry, Traffic Industry, Oil industry, Chemical industry,Coal Industry, Metallurgical Industry and so on.
Power supply
|
Rated input
|
AC/DC220V, or AC/DC110V
|
||
Range
|
Rated Voltage×(1±20%)
|
|||
Consumption
|
≤15VA ( DC )
|
|||
Rated Voltage
|
Rated input
|
AC 100V/100/√3V
|
||
Range
|
1~120V
|
|||
Accuracy
|
±0.5%
|
|||
Consumption
|
≤0.5VA (single phase)
|
|||
Rated Current
|
Rated input
|
AC 5A /1A
|
||
Range
|
0.04In~15In
|
|||
Accuracy
|
±0.5%
|
|||
Consumption
|
≤0.5VA (single phase)
|
|||
Frequence
|
Rated frequency
|
50Hz or 60Hz
|
||
Range
|
45~55Hz or 60Hz
|
|||
Accuracy
|
±0.1Hz
|
|||
DI
|
Rated Voltage
|
AC/DC220V, or AC/DC110V
|
||
Range
|
Rared Voltage×(1±20%)
|
|||
Consumption
|
≤1W(DC220V)(single channel)
|
|||
DO |
Mechanical life
|
≥10000
|
||
Switching capacity
|
≥1000W,L/R = 40ms
|
|||
On current
|
continuous ≥5A,short time (200ms) ≥30A
|
|||
Interrupting capacity
|
≥30W,L/R = 40ms
|
|||
Environment
|
Temperature
|
-10ºC~+55ºC
|
||
Humidity
|
5%~95% (No condensation and freeze inside)
|
|||
Altitude
|
≤2500m
|
Type
|
Main Function
|
Application
|
AM5-F
|
Directional overcurrent, overcurrent IDMT, earth fault, earth fault IDMT, overload, trip and close circuit supervision, loss of
voltage, PT supervision, three phase auto-reclose, under frequency, over frequency, Post-Accelerated overcurrent, overvoltage, residual overvoltage, directional power, FC block, RS485 (2 ports), modbus serial, IEC 60870-5-103,IEC 60870-5-101, tripping context records, SOE, electric parameter (U,I, P, Q,PF, F, Ep, Eq, Es), remote control, GPS. |
Line/Feeder
|
AM5-M
|
Overcurrent, overcurrent IDMT, earth fault overload, trip and close circuit supervision, undervoltage, PT supervision, blocking
rotor, residual overvoltage, non-electricity, starting time-out, thermal overload, negative sequence overcurrent, overvoltage average, overcurrent average, Incorrect phase sequence, FC block, RS485(2 ports), modbus serial, IEC 60870-5-103,IEC 60870-5-101, tripping context records, SOE, electric parameter (U, I, P,Q,PF, F, Ep, Eq, Es), remote control, GPS. |
Motor
|
AM5-B
|
Overcurrent, overcurrent IDMT, trip and close circuit supervision, PT supervision, Post-Accelerated overcurrent, bus tie
protection and standby power automatic switch, RS485(2 ports), modbus serial, IEC 60870-5-103,IEC 60870-5-101, tripping context records, SOE, electric parameter (U, I, P,Q,PF,F, Ep, Eq, Es), remote control, GPS. |
Bus tie
|
AM5-C
|
Overcurrent, overcurrent IDMT, earth fault, PT supervision, capacitor undervoltage, unbalance voltage, unbalance current, residual
overvoltage, non-electricity, FC block, RS485(2 ports), modbus serial, IEC 60870-5-103, IEC 60870-5-101, tripping context records, SOE, electric parameter (U,I, P,Q,PF, F, Ep, Eq, Es), remote control, GPS. |
Capacitor
|
AM5-T
|
Overcurrent, overcurrent IDMT, earth fault, earth fault IDMT, overload, trip and close circuit supervision, PT supervision,
non-electricity, FC block, RS485 (2 ports), modbus serial, IEC 60870-5-103,IEC 60870-5-101,tripping context records, SOE, electric parameter (U,I, P, Q,PF, F, Ep, Eq, Es), remote control, GPS. |
Transformer
|
AM5-U1
|
Undervoltage alarm, PT supervision overvoltage, residual overvoltage, RS485 (2 ports), modbus serial, IEC 60870-5-103, IEC
60870-5-101, tripping context records, SOE, electric parameter (U,I, P, Q,PF, F, Ep, Eq, Es), remote control, GPS. |
PT
|
AM5-U2
|
Undervoltage alarm, PT supervision, overvoltage, RS485 (2 ports), modbus serial, IEC 60870-5-103,IEC 60870-5-101, tripping context
records, SOE, electric parameter (U, I, P,Q,PF, F, Ep, Eq, Es), remote control, GPS. |
PT
|