Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 104.3/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Measured parameters | Voltage, current, frequency, active power, inactive power, power factor, active energy, inactive energy, 2nd-63rd harmonic, temperature, leakage | |
Voltage | Rated value | 3x220/380VAC |
Range | ±20% | |
Overloading | 1.2 times than the rated voltage value continuously or 2 times than the rated voltage value instantaneously per second | |
Current | CT | AMB100-A:5A/2.5mA, 100A/20mA, 400A/100mA, 600A/100mA AMB110-A:100A/20mA |
Range | 1%-120% | |
Overloading | 1.2 times than the rated current value continuously or 10 times than the rated current value instantaneously per second | |
Input frequency | 45-65Hz | |
Measurement accuracy | Voltage/current:grade 0.2; active power/energy:grade 0.5; inactive power/energy:grade 1; temperature:±1ºC | |
Auxiliary power supply | AMB100/110-A(/W):triggered upon receipt of request signal AMB100/110-A(/W)-P1:follow the bus bar voltage |
|
functions | Temperature detection | -20-150ºC |
Leakage | 0-1A | |
Digital input | 2 dry-contact inputs | |
Digital output | 2 relay outputs; contact capacity:3A/30VDC, 3A/250VAC | |
Communication | Via RS485/Modbus-RTU or LORA antenna | |
Installation | Use DIN35mm rail | |
Protection | IP20 | |
Pollution level | 2 | |
Environment | Temperature/ humidity/ altitude | Working temperature:-20-60ºC Storage temperature:-25-70ºC Relative humidity:≤93% Altitude:≤2500m |
Safety | Insulation | The minimum insulation resistance between all terminals and conductive components of the shell is 100MΩ. |
Withstanding voltage | When a voltage of 2kV AC is applied between the voltage/ current input, relay output, RS485 port, auxiliary power supply and digital inputs, the leakage shall be less than 2mA and no breakdown or flashover shall occur in 1min.. | |
Electromagnetic immunity | Electrostatic discharge immunity | Class 4 |
Radio frequency electromagnetic immunity | Class 3 | |
Transient burst immunity | Class 4 | |
Surge immunity | Class 4 |