Customization: | Available |
---|---|
After-sales Service: | Lifetime |
Warranty: | 2 Years |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AMC series programmable intelligent meters, adopting AC sampling technology, can directly or indirectly measure electric voltage and current of single phase or three phase grid. It can be used for local display, and connecting industrial control device to form measuring control system.
LCD Display;
1 x RS485 with programmable Modbus RTU;
Technical Parameter
|
Value
|
|
Input |
Rated Value
|
AC voltage:Single phaseAC 100V,400V
Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96) AC current:AC1A,5A; DC voltage:1000V,300V,75mV,10V; DC current: 0-20mA,4-20mA,5A; |
Overload
|
Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second
Current:1.2 times rated value(continuous); 10 times rated value /1 second |
|
Frequency
|
45Hz~65Hz
|
|
Power Consumption
|
Power consumption of each voltage,current input circuit is less than 0.5VA
|
|
Accuracy
|
Class 0.5
|
|
Function |
Display
|
LCD
|
Communication
|
RS485,Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity)
Baud Rate 2400/4800/9600/19200 bps etc. |
|
Alarm
|
1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc.
|
|
Analog
|
DC4~20mA,( load <500Ω)
(note:Shielded wire is specially selected for the above signal input and output) |
|
Switching
|
Input:4 channel or 2 channel dry contact Input,built in power supply
Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC |
|
Auxiliary Supply
|
AC/DC 85-265V
|
|
Power Consumption
|
<5VA
|
|
Insulation resistance
|
≥ 100MΩ
|
|
Power frequency withstand voltage
|
Between power supply set of terminals and signal input,output set of terminals 2kV/1min (RMS)
Between the shell and all set of terminals(except the set of terminals reference voltage less than 40V) AC 4kV |
|
Environment |
Temperature
|
Operation: -10ºC~+55ºCStorage: -25°C ~+70°C
|
Humidity
|
≤95%RH,no condensation,without corrosive gas
|
|
Altitude
|
≤ 2500m
|