Customization: | Available |
---|---|
Type: | Energy Meter |
Auxiliary Power: | AC/DC85-265V |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ADW210 series rail type multiloop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits. Up to four three-phase loop current inputs can be connected simultaneously. It can measure voltage and current, power,power factor, phase angle,unbalance, harmonic and other parameters.
Function
|
Description
|
|||
Energy Measurement |
kWh (positive and negative)
|
|||
kvarh (positive and negative)
|
||||
A,B,C three-phase positive kWh
|
||||
Electric Parameter
|
U, I, P, Q, S, PF, Hz
|
|||
Harmonic
|
2-31st voltage and current harmonic
|
|||
Communication
|
RS485 (MODBUS-RTU); baud rate 1200~38400
|
|||
Key Programming
|
4 keypads to set communication and parameters
|
|||
Display
|
LCD display, 8 digits
|
|||
LED Alarm
|
Over-voltage, over-current, interruption phase
|
|||
Data Log
|
Maximum demanded kWh and the time it happened.
|
|||
SOE
|
up to 200 pcs, record on-off status of DO/DI
|
|||
Pulse Output
|
Active optocoupler pulse output with open collector
|
|||
Multi-rate/Tariff
|
4 time zones & 12 time periods
|
Expanded Module
|
Description
|
|||
AWT100
Communication Module |
4G (Global general module)
|
|||
2G
|
||||
LoRaWAN (868 MHz, 923MHz)
|
||||
LoRa (460~510 MHz)
|
||||
NB-IoT
|
||||
-MK
Swtich Module |
12 × DI (input)
|
Dry contact input with built-in power supply
|
||
4 × DO (output)
|
Relay normally open contact output; rating AC 250V/3A ,DC 30V/3A
|
|||
Power Supply
|
DC 12V;consumption:≤1W;RJ45 interface
|
|||
Communication
|
RJ45 interface; MODBUS-RTU (communication with main body)
|
|||
-MTC
Temperature & Residual Current Measuring Module |
Temperature Measurement
|
-20ºC~+100ºC
|
||
Residual Current Measurement
|
10~3000 mA
|
|||
Accuracy
|
Temperature:± 2ºC; Residual Current:1% (Class 1)
|
|||
Power Supply
|
DC 12V;consumption:≤1W;RJ45 interface
|
|||
Communication
|
RJ45 interface; MODBUS-RTU (communication with main body)
|
|||
|
Parameters
|
Description
|
|||
Input
|
Voltage |
AC 3×220V/380V
|
||
Overload: 1.2 times of rated value (continuous); 2 times of rated
value / 1s |
||||
Power consumption:≤ 0.5VA
|
||||
Current |
AC 5A,100A,400A,600A;(external open-type CT)
|
|||
Overload: 1.2 times of rated value (continuous); 10 times
of rated value / 1s |
||||
Power consumption:≤ 0.5VA
|
||||
Frequency
|
45~65Hz
|
|||
Measuring
Accuracy |
Voltage&Current
|
Class 0.5
|
||
Active Power
|
Class 1
|
|||
Reactive Power
|
Class 2
|
|||
Frequency
|
0.05Hz
|
|||
2~31st harmonic
|
± 1%
|
|||
Auxiliary Power
|
AC/DC 85~265V;consumption≤10VA;
|
|||
EMC
|
Better than grade 3
|
|||
Safety
|
Withstand Voltage
|
>AC 2000V/1min
|
||
Insulation Resistance
|
>100MΩ
|
|||
Environment
|
Working Temperature
|
-20ºC~+60ºC
|
||
Storage Temperature
|
-40ºC~+70ºC
|
|||
Humidity
|
≤95% (No condensation)
|
|||
Altitude
|
≤2500m
|
|||
|
Paired CT
|
Primary Current
|
Secondary Current
|
Aperture(Hole size)
|
Accuracy Class
|
AKH-0.66/K-φ10N
|
5A
|
1.25mA
|
10mm
|
Class 0.5
|
AKH-0.66/K-φ16N
|
100A
|
20mA
|
16mm
|
Class 0.5
|
AKH-0.66/K-φ24N
|
400A
|
100mA
|
24mm
|
Class 0.5
|
AKH-0.66/K-φ36N
|
600A
|
100mA
|
36mm
|
Class 0.5
|
AKH-0.66-L-45 (for residual current)
|
/
|
/
|
/
|
Class 1
|