Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
APM5 series network power meter (hereinafter referred to as the meter) is designed according to IEC international standards, with full power measurement, power statistics, power quality analysis (including harmonics, flicker), fault recording function (including voltage temporary rise and fall interrupt, inrush current and other records), event recording function and network communication and other functions. It is mainly used for comprehensive monitoring of power supply quality in the power grid. This series of meters is equipped with feature-rich DI/DO modules, AO modules, wireless communication modules, leakage temperature measurement modules, which can flexibly realize the full electrical circuit Power measurement and switching status monitoring. Product model specifications and functions.
Measured
parameters |
Total electrical measurement
|
Four-quadrant energy,Split phase electricity,Apparent energy,Multi-rate energy
|
|
Pulse output of energy
|
Total active ,Total reactive energy pulse output (72 type only has active energy pulses)
|
|
|
Demand
|
Three-phase current, active power, reactive power, real-time demand of apparent power, and maximum demand (including time stamp)
|
Extreme
value statistics |
Current, line voltage, phase voltage, active power, reactive power and other electrical parameters extreme values of this month
and last month (including time stamps) |
Power quality |
Unbalance of current, line voltage, phase voltage
|
Voltage phase angle, current phase angle
|
|
Total (odd, even) harmonic content of voltage and current
|
|
Harmonic content of voltage and current (2-63 times)
|
|
Interharmonic (included with option S).
|
|
Flicker (included with S option).
|
|
Voltage peak coefficient
|
|
Telephone waveform factor
|
|
Current K-factor
|
|
Vector
|
|
Voltage and current waveform
|
|
Fundamental voltage and current
|
|
Fault waveform recording
|
Record of voltage ramp-up and drop interruptions, inrush currents, etc. (included with S option).
|
Event logging
|
DIDO records, which can record the last 128 DID records
|
Alarm logging
|
The last 128 alarm records can be recorded
|
Communication
|
Modbus - RTU protocol, DL/T 645-2007 statute
|
Switching value
|
72 Shape: 2 channels of switching input + 2 channels of switching output;
96 Shape: 4 switching inputs + 2 switching outputs |
Base model
|
Basic function
|
Optional function
|
Option Group
|
APM510
|
2DI2DO1EP1C
|
1. CE (Ethernet Communication/MODBUS-TCP).
|
1+5+6+7+8
2+3+4+7+8 5+6+7+8+9 5+6+7+8+10 5+6+7+8+11 5+6+7+8+12 |
2.2C (Extended 2nd Communication).
|
|||
3.K (2 switch inputs + 2 switch outputs).
|
|||
4.2M (2ch analog).
|
|||
5.T (4-channel NTC temperature measurement).
|
|||
6.L (1 channel leakage).
|
|||
7.F (Compound Rate).
|
|||
8.S (0.2S level + fault recording).
|
|||
9.WF(WiFi Communication)
|
|||
10.LR(Lora Communication)
|
|||
11.4G(4G Communication)
|
Base model
|
Basic function
|
Optional function
|
Option Group
|
APM520
|
4DI2DO2EP1C
|
1. CE (Ethernet Communication/MODBUS-TCP).
|
1+5+6+7+8
2+3+4+7+8 1+5+6+7+8 2+3+4+7+8 5+6+7+8+9 5+6+7+8+10 5+6+7+8+11 5+6+7+8+12 |
Display
|
Display method
|
Dot matrix liquid crystal; Switch between Chinese and English
|
|
Resolution
|
128*128;
|
|
|
Backlight
|
White LED;
|
|
|
Visible area
|
72 Shape: 38mm*46mm (1.78"/2.3");
96 Shape: 56mm*60mm (2.46"/3.2"); |
|
|
Signal
|
Electrical network
|
Three-phase three-wire, three-phase four-wire, see the wiring diagram;
|
|
Frequency
|
45~65Hz;
|
|
|
Voltage
|
Rating: AC 3*57.7/100V, AC 3*63.5/110V, AC 3*230/400V, AC 3*400/690V (96 Shape only);
|
|
|
|
Overload: 1.2 times the rating (continuous); 2x rating/1 second;
|
|
|
|
Power consumption: < 0.5VA(Every way);
|
|
|
Current
|
Ratings: AC 3x 1 (1.2) A, AC 3x5(6)A;
|
|
|
|
Overload: 1.2 times the rating (continuous); 10x rating/1 second;
|
|
|
|
Power consumption: < 0.5VA(Every way);
|
|
|
Measurement accuracy
|
Voltage, current
|
IEC 61557-12 0.2%
|
|
Measurement accuracy
|
Voltage, current
|
IEC 61557-12 0.2%
|
|
|
Voltage harmonics, current harmonics
|
IEC 61557-12 1%
|
|
|
Frequency
|
IEC 61557-12 ±0.02Hz
|
|
|
Active power
|
IEC 61557-12 0.5%
|
|
|
Reactive power
|
IEC 61557-12 1%
|
|
|
Active electrical energy
|
IEC 62053-22 0.5S class (0.2S accuracy when S is selected).
|
|
|
Reactive power
|
IEC 62053-24 Class 1
|
|
Power quality (only available when S is selected).
|
Waves recording
|
20 waveforms, 10 waves before and after;
|
|
|
Waveform capture
|
128 cycle points are stored per waveform;
|
|
Switch input
|
Dry contact input, built-in power supply;
Response time: less than 300ms |
||
Relay output
|
Contact type: normally open contact;
Contact capacity: AC 250V/3A DC 30V/3A; |
||
Energy pulse output
|
Output mode: photocoupler pulse with open collector;
Pulse constant: 10000imp/kWh (default); |
||
communication
|
RS485 interface/Modbus-RTU protocol and DLT645 protocol;
RJ45 interface (Ethernet)/Modbus-TCP protocol; Wireless interface |
||
power supply
|
Working range: AC 85V~265V; DC100V~350V
Power consumption: power consumption≤15VA; |
||
Safety
|
Power frequency withstand voltage
|
The power frequency withstand voltage between the housing and the auxiliary power supply, each input and output terminal group is
AC 4kV/1min; The power frequency withstand voltage between the auxiliary power supply and each input terminal and each output terminal group is AC 2kV/1min; The power frequency withstand voltage between the voltage input and other input and output terminal blocks is AC 2kV/1min; The power frequency withstand voltage between the current input and other input and output terminal blocks is AC 2kV/1min; The power frequency withstand voltage between the relay output and other input and output terminal blocks is AC 2kV/1min; The power frequency withstand voltage between the terminal groups of switching input, communication, analog output and pulse output is AC 1kV/1min; |
|
|
Insulation resistance
|
Inputs,outputs to the shell>100MΩ;
|
|
Electromagnetic compatibility
|
Complies with IEC 61000 standard (Level 4);
|
Environment
|
Operating temperature:-25ºC~+70ºC;Storage temperature:-40ºC~+85ºC;
Relative humidity:≤95% without condensation;Altitude:≤2500m; |
|
Protection Level
|
Display panel IP54; (Optionally IP65).
|
|
Standards
|
IEC 60068-2-1
IEC 60068-2-2 IEC 60068-2-30 |
Environmental Testing-Part 2-1:Tests Test A:Cold IDA
Environmental Testing Part 2-2:Tests Test B:Dry heat Environmental Testing Part 2-30:Tests Test Db:Damp heat,cyclic (12+12h) |
IEC 61000-4
|
Electromagnetic compatibility-Testing and measurement techniques
|
|
IEC 61557-12
|
Electrical safety in low voltage distribution systems up to 1 000V a.c. and 1 500V d.c -Equipment for testing, measuring or
monitoring of protective measures - Part12:Performances measuring and monitoring devices(PMD) |
|
IEC 62053-22
|
Electricity metering equipment (a.c.)-Particular requirements - Part22:Static meter for active energy(class 0.2S and 0.5S)
|
|
IEC 62053-24
|
Electricity metering equipment (a.c.)-Particular requirements - Part24:Static meter for reactive energy at fundamental frequency
(classes 0.5S 1S and 1) |