AID120 Alarm and Display Device
It is fit for embedding into operating room or nurse station internal wall installation which can monitor one set of AIM-M100 insulation monitoring device with the function of sound-light alarm on failures like insulation, overload, overtemperature and equipment failure etc. and digital display and RS485 communication.
AID120 is usually combined with AIM-M100, AID120 is usually used in combination with AIM-M100 for data exchange through RS485 communication.
4. Parameters
AUX POWER | Voltage | DC 24V |
Power consumption | ≤0.6W | |
Insulation measure range | 10…999kΩ | |
Insulation alarm range | 50…999kΩ | |
Transformer Load Rate | Percentage display | |
Current alarm range | 14A,18A,22A,28A,35A,45A | |
Temperature alarm range | 0…+200ºC | |
Alarm mode | Sound and light alarm | |
Alarm type | Insulation fault, overload, overtemperature, equipment failure | |
Communication mode | RS485,MODBUS-RTU | |
Display mode | LCD liquid crystal display,128*64 dot array |