Customization: | Available |
---|---|
After-sales Service: | 2 Years |
Warranty: | 2 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AMC Precision Power Distribution Monitoring Solution is a complete solution designed and developed for the monitoring requirements of precision power distribution cabinets (column head cabinets), including AC 220V and DC 48V/240V/336V systems: Composed of ≥ 7-inch touch LCD display screen, integrated information processing host module, switch status acquisition module, current transformer or Hall sensor acquisition unit module, etc AMC100 Precision Power Distribution Monitoring: Cabling and unplugging method, transformer rail installation, single module 30/48 circuits, system supports up to 4 incoming and 192 outgoing circuit monitoring.
Type Model
|
Function description
|
AMC100-ZA
|
Monitoring the full power parameters of the A+B dual three-phase AC incoming circuit, 8 switching status inputs, 4 switching
status outputs, 2 leakage monitoring, 1 temperature and humidity detection, 3 RS485 communications |
AMC100-FAK30 |
Monitor the full power parameters and switch status of a total of 30branches of A+B dual AC outlets, and 1 RS485 communication
|
AMC100-FAK48 |
Monitor the full power parameters and switch status of a total of48branches of A+B dual AC outlets, and 1 RS485 communication
|
AMC100-FA30
|
Monitor the full power parameters of a total of 30branches of A+B dual AC outlets, and 1 RS485 communication
|
AMC100-FA48
|
Monitor the full power parameters of a total of48branches of A+B dual AC outlets, and 1 RS485 communication
|
AMC100-KA30 |
Wet contact, monitor the switching status of 30branches A+B, 1 RS485 communication
|
AMC100-KA48 |
Wet contact, monitor the switching status of 48branches A+B, 1 RS485 communication
|
AMC100-KD30 |
Dry contact, monitor the switching status of 30branches A+B, 1 RS485 communication
|
AMC100-KD48 |
Dry contact, monitor the switching status of 48branches A+B, 1 RS485 communication
|
AMC100-FT30
|
1 way RS485 communication, 30 way temperature measurement
|
AMC100-FT48
|
1 way RS485 communication, 48 way temperature measurement
|
Function
|
Description
|
Measurement
(Common) |
Three-phase AC kWh, kVarh, Active Power, Reactive Power, Current, Voltage, Power Factor, Apparent Power, Frequency, Zero ground
voltage, neutral line current |
Measurement
(Power Quality) |
total harmonic content (THD), 2-63 harmonics, current and voltage unbalance degree, current K coefficient (KF), voltage crest
coefficient (CF), telephone waveform factor (THFF), peak voltage, voltage and current sequence quantity |
Temp.&Humidity
Monitoring |
Temperature Monitoring Range: -40ºC~+99ºC
Humidity Monitoring Range: 20%~90% |
Leakage Current
|
2-channel Leakage Current Measurement
|
Accuracy
|
Electrical Parameter Metering Accuracy: Voltage/current level 0.2, active power/electric energy level 0.5, reactive power/electric
energy level 1 Temperature Metering Accuracy: ±1ºC; Temperature Metering Accuracy: ±5% |
Communication
|
RS485 Interface (MODBUS-RTU protocol)
|
DO
(Switch Output) |
2-channel DO (Digital Output); 3A 250VAC/3A 30VDC
|
DI
(Switch Input) |
6-channel DI (Digital Input); dry contact
|
Parameter
|
Description&Value
|
|
Voltage
Input |
Rated Voltage
|
3x220~264Vac L-N
|
Reference Frequency
|
45~65Hz
|
|
Current
Input |
Rated Current
|
3x1(6)A AC (via CTs)
|
Power
Supply |
Source from
|
Voltage Input (Voltage signal input for both measurement and power supply)
|
Installation
|
DIN-rail
|
35mm standard DIN-rail Installation
|
Phase
Wiring |
3P4W
|
3-phase 4-wire
|
Safety
|
Insulation
|
All terminals and the insulation resistance between the conductive pieces not less than 100MΩ
|
Withstand voltage
|
A-way voltage and current signal, B-way voltage and current signal, switch output and other ports should meet AC2kV 1min in pairs,
the switch input and other ports should meet ac0.5kv 1mim, leakage current should be less than 2mA, no breakdown or flashover |
Condition
|
Description&Value
|
Temperature
|
Operating Temperature: -20ºC~+55ºC; Storage Temperature: -40°C ~+70°C
|
Humidity
|
≤95%RH, no condensation, without corrosive gas
|
Altitude
|
≤ 2000m
|