Customization: | Available |
---|---|
Warranty: | 2 Years |
Installation: | Direct Connected |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
ADW200 rail-type multi-circuit power meter is mainly used for various three-phase power parameter measurement and active and reactive power measurement of low-voltage network. It can select current input of up to four circuits at the same time. It has RS485 communication and 470MHz wireless communication functions. It can also be used with a variety of expansion modules to facilitate users to monitor, collect and manage electricity consumption. It can be flexibly installed in the distribution box to achieve sub-item power measurement, statistics and analysis of different areas and different loads.
Auxiliary power
|
|
AC/DC 85~265V; Consumption≤10VA;
|
||
Input |
Frequency
|
45~65Hz;
|
||
Voltage
|
AC 3×220V/380V; Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s; Power consumption: ≤ 0.5VA;
|
|||
Current
|
AC 5A,100A,400A,600A;(External opening transformer); Power consumption: ≤ 0.5VA; Overload: 1.2 times of rated value (continuous);
10 times of rated value / 1s; |
|||
Measurement Accuracy
|
Frequency 0.05Hz, voltage,current Class 0.5; 2-31st harmonic accuracy: ± 1%; Active electric energy level 1, reactive electric
energy level 2; |
|||
Features
|
Pulse Output
|
Output mode: optocoupler pulse with open collector;
|
||
Communication
|
RS485,Modbus-RTU; Baud rate 1200~38400;
|
|||
Switching Input
|
Dry contact input,Built in power supply;
|
|||
Switching Output
|
Output mode: Relay normally open contact output; contact rating: AC 250V/3A DC 30V/3A;
|
|||
Switching Module
|
Power
|
RJ45 interface,DC 12V,Power consumption≤1W;
|
||
Communication
|
RJ45 interface,Modbus-RTU;(Communication with the main Part)
|
|||
Switching input
|
Dry contact input,Built in power supply;
|
|||
Switching output
|
Output mode:Relay normally open contact output; contact rating:AC 250V/3A DC 30V/3A;
|
|||
Temperature and leakage module
|
Power
|
RJ45 interface,DC 12V,Power consumption≤1W
|
||
Communication
|
RJ45 interface,Modbus-RTU;(Communication with the main Part)
|
|||
Temperature measurement
|
-20~100ºC;
|
|||
Leakage measurement
|
10~3000mA;
|
|||
Measurement accuracy
|
temperature ±2ºC,Leakage1.0%;
|
|||
Safety
|
Power frequency withstand voltage
|
>AC 2kV/1min;
|
||
Insulation resistance
|
>100MΩ;
|
|||
Environment
|
Working temperature: -20ºC~+60ºC; Storage temperature: -40ºC~+70ºC; Relative humidity: ≤95% No condensation; Altitude: ≤2500m;
|
|||
Electromagnetic compatibility
|
Better than grade 3;
|