Customization: | Available |
---|---|
Warranty: | 2 Years |
Display: | Indicator |
Still deciding? Get samples of US$ 133/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
(Note: The meter can match to Solis Inverter to solar power zero export, if it is used for the Solis Inverter)
|
Measurement: 3-phase Active Power, Reactive Power, Current, Voltage and etc
Current Rating:
Diameter 10mm,80A (paired with 3 external CTs)
Diameter 16mm,120A (paired with 3 external CTs)
Diameter 24mm,200A (paired with 3 external CTs)
Diameter 36mm,300A (paired with 3 external CTs)
Communication: RS485 (MODBUS-RTU)
Application: Using distributed Solar PV and Anti-reflux Inverter
Display: LCD Display
Dimension: 54*64*84mm (L*W*H)
Installation: 35mm DIN Rail
Power Supply: 85~265V AC or 100~350V DC
Standard&Certificate: CE
optional function: Harmonic Monitoring
|
|
Used for distributed Solar PV Reflux Monitoring |
|
Bidirectional Metering Active Energy Metering Reactive Energy Metering |
|
RS485 Communication MODBUS-RTU Protocol Communicate with Inverter to realize anti-reflux Function |
Paired with external CTs or Rogowski Coil Rated Current of CTs: up to 300A Rated Current of Rogowski Coil: up to 20000A |
|
|
LCD Display Parameter Display Programming Interface |
|
Keypads HMI for Programming Parameter Display Setting Communication(address, baud rate and etc.) Wiring: 3P3W,3P4W |
Technical parameters
|
Indicators
|
|||
Input
|
Net work
|
3-phase 3-wire,3-phase 4 wire
|
||
|
Frequency
|
45~65Hz
|
||
|
Voltage
|
Rating:AC 57.7V/100V(100V),220V/380V(400V)
|
||
|
|
Overload:1.2-fold rating(continuous);2-fold rating/1second
|
||
|
|
Consumption:<0.2VA
|
||
|
Current
|
Rating: 80A,120A,200A .etc(See specific product specifications,special parameters can be customized)
|
||
|
|
Overload:1.2-fold rating(continuous);10-fold rating/1 second
|
||
|
|
Consumption:< 0.2VA
|
||
Output
|
Electric energy
|
Output mode: Open-collector photocoupler pulse, two-way output
|
||
|
|
Three-phase
|
Pulse constant:4000,8000imp/kWh
|
|
|
Communication
|
RS485 interface, Modbus-RTU Protocol
|
||
|
Display mode
|
LCD
|
||
Function
|
Switching
|
Input
|
Four-way dry contact input
|
|
|
|
Output
|
Output mode: two-way relay nO contact output
|
|
|
|
|
Contact capacity:AC 250V/3A,DC 30V/3A
|
|
Measuring accuracy
|
Frequency0.05Hz,reactive electric energy1class,other 0.5class
|
|||
Power supply
|
AC85~265V or DC100~350V;DC24V(±10%);DC48V(±10%) Consumption≤10VA
|
|||
Safety
|
Power-frequency withstand voltage
|
Power frequency withstands voltage between Auxiliary power and switch volume output and current input and voltage input and communication and pulse output and switch volume input terminal is AC2kV 1min; Power frequency withstand voltage between auxiliary power and switch volume output and current input voltage input terminal is AC 2kV/1min; Power frequency withstand voltage between communication and pulse output and switch volume input terminal is AC 1kV/1min;
|
||
|
Insulation resistance
|
Input, Output terminal to housing>100MΩ
|
||
Environment
|